Sunday, November 24, 2013

ACI 318-11 thicker stronger shotcrete pools

ACI 318-11 requires that the shotcrete walls on salt water pool be increased in strength and thickness.  Shotcrete is defined as either the wet or dry process of pneumatically placing concrete.

ACI - The American Concrete Institute

ACI is the definitive expert on concrete.  So much so, that they publish a myriad of standards that relate to concrete and it's use.

ACI Standard 318-11, "Building Code Requirements for Structural Concrete" has been directly incorporated into the International Building Code (adopted by 48 States, except Minnesota) and by the California Building Code.  This effectively makes it the law of the land. 

ACI 318-11 changes the requirements

ACI 318-11 redefined the parameters of the required coverage of concrete required over the reinforcing steel.  Prior versions of ACI 318 were ambiguous as to what was actually defined as sulfate or corrosive conditions.

ACI 318-11 establishes the additional shotcrete protection required when exposed to defined levels of sulfates, water containing chlorides (salts) and permeability.

ACI 318-11, Table 4.2.1 indicates that shotcrete swimming pools are required to meet the criteria for Permeability - P1 (condition defined as: "in contact with water where low permeability is required") AND Corrosion Resistance - C2 ( a condition defined as: "concrete exposed to moisture and an external source of chlorides from
deicing chemicals, salt, brackish water, seawater, or spray from these sources").


The resulting P1 and C2 classifications require specific mix design ratios (ACI 318-11, Table 4.3.1).

ACI 318-11, Table 4.3.1, P1 classification sets a maximum water to cement ratio (w/cm2) of 0.50 and a MINIMUM 28 day compressive strength (f'c) of 4,000 PSI.  While the C2 classification establishes a maximum water to cement ratio (w/cm2) of 0.40 and a MINIMUM 28 day compressive strength (f'c) of 5,000 PSI.

Therefore, any swimming pool that is going to be treated with sodium compounds is REQUIRED to have a maximum water to cement ratio (w/cm2) of 0.40 and a designed compressive strength (f'c) of 5,000 PSI.  Sodium compounds utilized in swimming pool sanitization include sodium chloride (chlorine), sodium bromide (bromine) or sodium (salt-electrolysis chlorination).

The C2 classification (Table 4.3.1) further specifies that the requirements of ACI 318-11, 7.7.6 "Corrosive Environments" be met.  Section 7.7.6 states that the coverage over reinforcing steel shall not be less than 2 inches for walls and slabs subject to such corrosive environments.

Structural Engineers & Building Departments

Many structural engineers and building departments do not abide by the requirements of ACI 318-11.  They either attempt to justify design criteria less than the standards, are not versed on the most up to date requirements or simply fail to comply with the codes.

When there is an issue of structural integrity on your pool, the most recently adopted version of the IBC, CBC or ACI standards will apply in court, whether or not they were enforced by the engineer or building inspector.

Do you want to be left hanging with a structural engineer who will have to defend his decision to design a structure that was below the requirements of the building codes?  
Do you want to take the risk that he will be able to convince a jury of lay people that a weaker structure is acceptable?

I thought not!

Contact the author, Paolo Benedetti of Aquatic Technology Pool and Spa at: info@aquatictechnology.com or 408-776-8220. 
Visit his website at: www.aquatictechnology.com. 
All Contents © Aquatic Technology Pool & Spa, 2013. 
All rights reserved.

Wednesday, September 4, 2013

Swimming Pool Expert Witness - Honesty

Honesty from a swimming pool expert witness is paramount!

An Issue of Credibility

False claims of experience by a swimming pool expert witness will only serve to impeach their credibility.

There are a number of swimming pool expert witnesses who are claiming to have been involved in the design, engineering or construction of tens of thousands of swimming pools.

Delve into the Facts

Was the expert witness the principal of an "engineering mill," that sold generic pool plans via mail order to anyone with a checkbook?  Does that permit them to claim those as experience? Claiming to have been involved in every one of those projects? Hardly!

Was the expert witness the president of a large franchise swimming pool company?  Because they delivered generic engineering to their franchisees, do they get to claim that as "involvement?" Does that allow them to claim that they were involved in every project that their independent franchise owners built?  Hardly!

Issues of Quality

Are there issues of quality or compliance surrounding pools build using those generic plans?  

The issuance of such plans by a licensed engineer without reviewing the site or soils conditions, is a violation of the International Building Code (the USA's National Building Code).  Structures must be designed to withstand the site conditions - something that the structural engineer cannot do without reviewing a soils report or the site conditions.

Have any projects that utilized those generic plans ever experienced structural failures?  
Were those failures due to the inadequacies of the plans or the lack of review of the site or soil conditions?  
Maybe the plans that were provided were inappropriate for the conditions that were present?
Were there quality or construction defect issues with any of the pools built by franchisees?  

If an expert witness is going to claim those projects as their "qualifying experience," then don't they also have to assume the failures associated with those very same projects?

It's all a matter of veracity.

Contact the author, Paolo Benedetti of Aquatic Technology Pool and Spa at: info@aquatictechnology.com or 408-776-8220. 
Visit his website at: www.aquatictechnology.com. 
All Contents © Aquatic Technology Pool & Spa, 2013. 
 All rights reserved.

Monday, September 2, 2013

Concrete Filling Drilled Caissons - Don't just let the concrete fall

Filling drilled caissons with concrete - do not just let the concrete fall!

Free Fall

Recently, I was asked to weigh in on a project where the methods for placing concrete into drilled caissons were under debate.  

The concrete contractor insisted that the concrete could be dropped from the surface down into the 40 foot hole.  The swimming pool contractor did not feel comfortable with that, but did not know of any standards that dictated otherwise.

American Concrete Institute (ACI)

The ACI publishes a myriad of concrete standards.  Most issues regarding concrete, are discussed in their standard ACI 318.  ACI 318 has been adopted and incorporated into the International Building Code (IBC) as well as the California Building Code (CBC).  The IBC is the basis for building codes relating to concrete, that have been adopted across the nation.

ACI 318 states that concrete should be placed as close to it's intended location as possible.  So, in the case of drilled caissons, that means filling the hole from the bottom up.  The weight of 40 feet of 3-4" concrete filled hose is unwielding.  Usually a crane, backhoe or concrete boom is required to fill such deep holes.

California Building Code

The CBC is a little more compromising.  It allows for the concrete to fall no more than 6 feet.

Separation

Why is there any concern at all?  Separation.

If the concrete is allowed to fall a significant distance, the aggregate separates from the concrete.  A homogenous mix is not delivered to the final resting place.  Pumping the concrete from 40 feet also allows the concrete to bounce off of the reinforcing steel, also separating the aggregate from the cement.

To ensure that the specified mix design is delivered as specified, precise placement practices are critical.  

 
Contact the author, Paolo Benedetti of Aquatic Technology Pool and Spa at: info@aquatictechnology.com or 408-776-8220. 
Visit his website at: www.aquatictechnology.com. 